Marking |
Function |
SET |
Page Down, modify, confirm ,save |
RIGHT |
Shift |
UP |
Add ,page up |
ESC |
Exit (quit without saving) |
(1) Function Area
Marking |
Description |
|
Battery Capacity |
|
Powered by 24V DC or loop powered |
|
RS485 Communication, send display,receive display |
The main display will jump to supplementary display after 60s, and the supplementary display will jump to main display automatically after 3s. The supplementary display can show time, signal frequency and current parameters.
When the display in supplementary display, please press SET keys to input passwords.
When input the wrong passwords, users can view P1-P19 parameters, but cannot modify them.
Switch Position |
Picture |
Function |
1-ON;2-OFF;3-OFF |
|
1. Unscaled pulse output 2. Standard 0-1000Hz output 3. Revised frequency output (Refer to P2 display) |
1-OFF;2-ON;3-OFF |
|
Scaled pulse output |
1-OFF;2-OFF;3-ON |
|
Unscaled pulse output |
Note:
a. DIP switch corresponds to frequency output port FOUT
b. Unsacled pulse output is the pulse not compensate by flow meter factor, modified pulse is the pulse which compensated by the instrument’s factor.
c. Scaled pulse is recommended not set high resolution ratio, and not large pulse width to avoid output saturation.
For example: DN50 Gas turbine flow meter, flow range 6-65 m3/h, P-1 set 0.001,scaled pulse set 50ms,that means when there is 0.001 Nm3 total flow, it will output a scaled pulse with width 50ms, 50% duty cycle, the max frequency is 1000/(50*2)=10Hz, the corresponding max flow is 0.001 *10*3600=36 Nm3/h, that is when the instant flow over 36N m3/h, the output scaled pulse frequency is still 10 Hz, that is output saturation.